Cimon.Net

NuGet NuGet Downloads CI CodeQL .NET Standard 2.0 .NET 8 License: MIT

A lightweight .NET library for communicating with CIMON PLCs over Ethernet (TCP) and Serial (RS232C / RS485). Read and write bits and words in PLC device memory with a simple async API.

using var plc = new EthernetConnector(new TcpSocket("192.168.1.10"));
var (code, words) = await plc.ReadWordAsync(MemoryType.D, "000100", 10);

Contents

About

CIMON PLCs are industrial controllers based on the IEC 61131 standard. There are many tools and servers to exchange data with PLCs, but what if you want your own application to talk to them directly? I couldn't find any library for CIMON PLCs, even though I used them in many projects, so I decided to publish mine.

Features

  • Ethernet (TCP) and Serial (RS232C / RS485) connectors with the same API
  • Read and write bits and words in any device memory (X, Y, M, L, K, F, T, C, S, D)
  • Fully async, and safe to share one connector between concurrent tasks
  • Responses are validated (header, frame number, checksum and length) before data is returned
  • Automatic or manual connection management
  • Targets .NET Standard 2.0 and .NET 8, so it runs on .NET Framework 4.6.1+ as well as modern .NET
  • No third-party dependencies besides System.IO.Ports

Installation

Install from NuGet with the .NET CLI:

dotnet add package Cimon.Net

Or with the Package Manager Console in Visual Studio:

Install-Package Cimon.Net

Quick start

Create a connector for your connection type: EthernetConnector for Ethernet TCP, or SerialConnector for RS232C/RS485.

Ethernet

using CimonPlc.Enums;
using CimonPlc.PlcConnectors;
using CimonPlc.Sockets;

using var plc = new EthernetConnector(new TcpSocket("192.168.1.10", 10620));

// Read 10 bits from input memory X, starting at address 000001
var (responseCode, bits) = await plc.ReadBitAsync(MemoryType.X, "000001", 10);

if (responseCode == ResponseCode.Success)
    Console.WriteLine(string.Join(", ", bits));

// Write 3 words to data register D, starting at address 000100
var writeResult = await plc.WriteWordAsync(MemoryType.D, "000100", 1200, 35, 65535);

Serial

using var plc = new SerialConnector(new SerialSocket("COM3", 9600));

// Write 5 bits to output memory Y, starting at address 000010
var responseCode = await plc.WriteBitAsync(MemoryType.Y, "000010", 1, 1, 1, 0, 1);

// Read 4 words from data register D
var (code, words) = await plc.ReadWordAsync(MemoryType.D, "000200", 4);

API overview

Method Returns Description
ReadWordAsync(memoryType, address, length) (ResponseCode, int[]) Reads length 16-bit words
ReadBitAsync(memoryType, address, length) (ResponseCode, byte[]) Reads length bits, each value is 0 or 1
WriteWordAsync(memoryType, address, params int[] data) ResponseCode Writes words, each value in 0–65535
WriteBitAsync(memoryType, address, params byte[] data) ResponseCode Writes bits, each value 0 or 1
Connect(readTimeout, writeTimeout, pingTimeout) ConnectionStatus Opens the connection (timeouts in ms, 100–10,000)
Disconnect() ConnectionStatus Closes the connection

Invalid arguments (bad address format, out-of-range length or values) throw ArgumentException. Communication problems are reported through the returned ResponseCode.

Connection handling

With autoConnect enabled (the default), each read or write opens the connection if needed and closes it afterwards. That's convenient for occasional requests. For frequent polling it's much faster to keep one connection open:

using var plc = new EthernetConnector(new TcpSocket("192.168.1.10"));

var status = await plc.Connect(readTimeout: 1000, writeTimeout: 1000, pingTimeout: 3000);
if (status != ConnectionStatus.Connected)
    return;

while (!cancellationToken.IsCancellationRequested)
{
    var (code, words) = await plc.ReadWordAsync(MemoryType.D, "000100", 10);
    // ...
    await Task.Delay(500);
}

plc.Disconnect();
  • A connection opened with Connect() stays open, even when autoConnect is enabled.
  • With autoConnect: false, requests on a closed connection return ResponseCode.SystemError.
  • Requests on one connector are sent one at a time, so a single connector can be shared between tasks.
  • By default, TcpSocket pings the PLC before connecting and returns ConnectionStatus.NoRouteToDestination if there's no reply. If your network blocks ICMP, turn the ping off:
var socket = new TcpSocket("192.168.1.10", 10620, usePing: false);

Addresses and memory types

Addresses are hexadecimal strings of up to 6 characters. Shorter addresses are padded with leading zeros, so "A0" becomes "0000A0".

  • Word functions need a word address, so the last digit must be 0 (for example "000010").
  • Bit functions accept any bit address (for example "0000A1").
Memory Name Description
X Input Inputs received directly from devices
Y Output Outputs written to devices
M Internal memory Internal relays used by the logic
L Link Data link with upper and lower devices
K Keep Like M, but retained when power is off
F Internal flag System state, clock contacts and flags
T Timer Timer values
C Counter Counter values
S Step control Step control relays
D Data register Internal data storage

Response codes

Every request returns a ResponseCode. Anything other than Success means the request failed.

Code Value Meaning
Success 0 Request processed successfully
SystemError 1 System error, no connection or no response from the PLC
InvalidDevicePrefix 2 Invalid device prefix
InvalidDeviceAddress 3 Invalid device address
UdpErrorReadDataSize 4 Error in requested data size
UdpErrorBlockSize 5 More than 16 requested blocks
BufferError 6 Buffer memory reported an error in data or size
OverBufferCapacity 7 Receive buffer capacity exceeded
OverSendingTime 8 Sending time exceeded
UdpInvalidHeader 9 Invalid header
ChecksumError 10 Checksum error in the received data
FrameSizeError 11 Error in frame length
UdpDataSizeError 12 Error in the size of data to write
UnknownBitValue 13 Invalid bit value in write data
UnknownCommand 14 Unknown command
WritingError 15 Writing is disabled, or the response was invalid
CpuError 16 CPU processing error

Limits per request

Function Ethernet Serial
ReadWordAsync 1–512 words 1–63 words
ReadBitAsync 1–1024 bits 1–126 bits
WriteWordAsync 1–64 words 1–61 words
WriteBitAsync 1–256 bits 1–126 bits

Supported PLCs and platforms

  • PLCs: the CIMON PLC range, including the PLC-S, CP and XP series
  • Frameworks: .NET Standard 2.0 (.NET Framework 4.6.1+, .NET Core 2.0+, Mono) and .NET 8+

More documentation is in the Wiki.

Build and test

You need the .NET SDK 10 or newer.

dotnet build
dotnet test

No PLC is needed. EthernetConnector tests talk over real TCP sockets to a PLC simulated with the Rony.Net mock server, and SerialConnector tests use a fake serial socket.

The Ethernet tests are also a sample of testing a binary protocol client with Rony.Net:

  • PlcMockServerTest uses Rony.Net.Xunit to give every test its own server on a free port, with its log in the test output.
  • CimonFraming is a custom IMessageFraming that splits the TCP stream into Cimon frames.
  • CimonPlcSimulator answers like a PLC and keeps its memory, so written values can be read back.
  • EthernetFailureTests simulates slow, chunked, truncated, corrupted and dropped responses.
Plc.Attach(Server);                                   // answer like a PLC
using var connector = CreateConnector();              // EthernetConnector for 127.0.0.1:Server.Port

await connector.WriteWordAsync(MemoryType.D, "100", 1, 2, 3);
var (code, words) = await connector.ReadWordAsync(MemoryType.D, "100", 3);   // [1, 2, 3]

Server.Should().HaveAcceptedConnections(Times.Exactly(2))   // autoConnect: one connection per request
    .And.HaveReceivedInOrder(
        r => r.Body[10] == (byte)WriteCommands.WordBlockWrite,
        r => r.Body[10] == (byte)ReadCommand.WordBlockRead);

Contributing

Issues and pull requests are welcome. Please run dotnet test before opening a pull request, and add tests for new behavior. See CHANGELOG.md for the release history.

License

Cimon.Net is released under the MIT License.