Deterministic PV hosting-capacity screening for distribution feeders, built on pandapower.
Built-in 0.4 kV LV feeder, worst-hour snapshot (minimum load / maximum PV):
At the 43.31 kW system limit the far-end bus LV6 hits 1.0503 p.u. — overvoltage binds first, exactly where the diagnostics say it does.
Each bus on its own: LV1 next to the transformer hosts 102.9 kW, LV6 at the far end only 25.8 kW — the map a DSO actually needs for connection offers.
Same feeder, four strategies: an OLTC tap move (−5% on the LV side) lifts system HC by 52.8% (43.31 → 66.19 kW), while "smart" Q(U) droop adds only 2.2% here.
How much rooftop PV can a feeder take before something breaks — and where
exactly does it break first? pvhostcap answers both with a fast,
deterministic screening workflow: a bisection search over PV size against
voltage and thermal limits, for the whole feeder and bus by bus.
The heavyweight options exist — NREL's disco (HPC-scale, OpenDSS-based), stochastic Monte-Carlo studies, MILP optimal-sizing formulations. They are powerful but slow to set up and overkill for the industry's actual first step: the deterministic worst-hour screening (minimum load / maximum PV) that decides whether a feeder needs a deeper study at all (see Mulenga et al., 2020 for the method taxonomy).
pvhostcap fills the lightweight end:
- pandapower-native — no OpenDSS, no MILP solver, plain Newton-Raphson load flow. A full feeder screening runs in seconds.
- Two questions, not one — the system HC (uniform PV spread) and the locational HC map: how much each individual bus can host on its own. The locational map is what a DSO actually needs for connection offers, and it is the output most screening scripts skip.
- Binding-constraint diagnostics — every result names the exact bus or line that binds and by how much, so you know why the number is what it is.
- Connection-offer check —
connection_check(net, "LV4", 15.0)answers the DSO's everyday question directly (bus name or index in, approved/denied plus the blocking violations out), without re-running a search. - Mitigation comparison built in — re-run the same search under classic enhancement measures (reactive-power control, OLTC tap change) and see the HC gain side by side.
- Build (or supply) a radial feeder as a pandapower net.
- Evaluate one PV allocation: attach PV as static generators, run the load
flow, check
vmax/ line / transformer limits. A non-converged load flow counts as infeasible. - System HC: bisect on the uniform per-bus PV size. Feasibility is monotone decreasing in PV size, so bisection is exact up to the tolerance.
- Locational HC: repeat the bisection per bus, all other buses at zero PV.
- Mitigations: the same search with a strategy applied before each load flow — constant-PF absorption, Q(U) Volt-VAr droop (fixed-point iteration), or an OLTC tap move.
Assumptions are stated up front: single worst-hour snapshot, balanced three-phase model, PV allocated per load bus (rooftop-PV screening convention). Uncertainty and time series are deliberately out of scope — see the references for those treatments.
pip install pandapower matplotlib
pip install git+https://github.com/chenyi6758-source/pvhostcap.git # or: pip install -e . from a checkout
python examples/quickstart.pyfrom pvhostcap import (
build_lv_radial, system_hosting_capacity,
locational_hosting_capacity, compare_strategies,
connection_check,
)
net, load_buses = build_lv_radial() # built-in 0.4 kV test feeder
hc = system_hosting_capacity(net, load_buses)
print(hc)
# HC = 43.31 kW total (7.22 kW x 6 buses), binding: overvoltage at bus LV6
loc = locational_hosting_capacity(net, load_buses) # weak-bus map
comp = compare_strategies(net, load_buses) # mitigation comparison
# the DSO's everyday question: can LV4 take 15 kW of new rooftop?
approved, violations = connection_check(net, "LV4", 15.0)
print(approved) # True — LV4 alone hosts up to 36.1 kWexamples/quickstart.py runs the full workflow end to end and saves the
figures below into examples/output/.
Built-in LV feeder (0.4 kV, six load buses, NAYY 4x50 SE cables):
| analysis | result |
|---|---|
| System HC | 43.31 kW (7.22 kW × 6 buses) |
| Binding constraint | overvoltage at bus LV6 (far end): 1.0503 p.u. |
| Locational HC | LV1 102.9 → LV2 60.4 → LV3 44.8 → LV4 36.1 → LV5 30.2 → LV6 25.8 kW |
Mitigation comparison on the same feeder:
| strategy | system HC | vs baseline |
|---|---|---|
| none (baseline) | 43.31 kW | — |
| fixed power factor 0.95 (absorb) | 46.31 kW | +6.9% |
| Q(U) Volt-VAr droop | 44.25 kW | +2.2% |
| OLTC tap −5% on LV side | 66.19 kW | +52.8% |
The MV feeder (10 kV, five 400 kW load buses) tells the opposite story: system HC 7.60 MW, binding on the head-end line thermal limit (100.4%), voltage only reaching 1.03 p.u. — the same tool, a different bottleneck, which is exactly what the diagnostics are for.
- On the LV feeder, constant-PF absorption beats Q(U) droop (+6.9% vs +2.2%). The droop only acts above its 1.03 p.u. deadband, so near-transformer inverters contribute nothing — a reminder that "smart" control is not automatically better; it depends on the feeder.
- The OLTC move dominates (+52.8%) because this feeder is purely voltage-bound. On the thermally-bound MV feeder it does nothing.
- Deterministic screening is optimistic by construction: it ignores load/PV uncertainty and phase imbalance. Treat the numbers as a first-pass screen, not a connection guarantee.
pip install -e ".[test]"
pytest # 33 tests, incl. physics checks:
# far-end bus is weakest, mitigations never hurt HC,
# LV feeder voltage-bound / MV feeder thermal-bound,
# input validation, connection-check by bus name- Brohi, N.A. et al. "Advances in Hosting Capacity Assessment and Enhancement Techniques for Distributed Energy Resources: A Review of Dynamic Operating Envelopes in the Australian Grid." Energies 18(11), 2922 (2025). — method taxonomy (deterministic / stochastic / time-series / AI-based) and enhancement techniques.
- Mulenga, E., Bollen, M.H.J., Etherden, N. "A review of hosting capacity quantification methods for photovoltaics in low-voltage distribution grids." Int. J. Electr. Power Energy Syst. 115, 105445 (2020). — the deterministic-screening baseline this tool implements.
- Bollen, M.H.J., Hassan, F. Integration of Distributed Generation in the Power System. Wiley-IEEE Press (2011). — the original "hosting capacity approach".
- Shen, C. et al. "Kullback–Leibler Divergence-Based Distributionally Robust Chance-Constrained Programming for PV Hosting Capacity Assessment." Scientific Reports (2024). — how the literature handles PV uncertainty; explicitly out of scope here.
Related open-source work: NREL disco (HPC-scale HC analysis), skortmann/probabilistic-pv-hosting-capacity (probabilistic, SimBench LV grids).