Original file line number Diff line number Diff line change
Expand Up @@ -163,8 +163,26 @@ jobs:
- uses: actions/download-artifact@v4
with:
path: artifacts
# Every platform artifact carries the same docs (README.md, LICENSE, ...).
# Uploading two assets with one name makes the release action fail part-way
# and leaves a draft release behind (a real tagged release hit this). Flatten the
# artifacts into one folder with a single copy of each file name, and stop
# if two files share a name but differ.
- name: Collect release assets (one copy of each file name)
shell: bash
run: |
mkdir -p release
find artifacts -type f | sort | while read -r f; do
name=$(basename "$f")
if [ -e "release/$name" ]; then
cmp -s "$f" "release/$name" || { echo "FAIL: two different files are both named $name ($f)"; exit 1; }
else
cp "$f" "release/$name"
fi
done
ls -l release
- uses: softprops/action-gh-release@v2
with:
name: ${{ github.ref_name }}
generate_release_notes: true
files: artifacts/**/*
files: release/*
2 changes: 1 addition & 1 deletion AGENTS.md
Original file line number Diff line number Diff line change
Expand Up @@ -83,7 +83,7 @@ up/down nudge Analog Input 1.

## Conventions

- Device is named "Rainbow"; objects use the series' colour names; vendor id
- Device is named "Chipkin Example B-SS"; objects use the series' colour names; vendor id
389.
- Implement **only** the services and objects the B-SS profile requires -
but expose **every required property** of each object.
Expand Down
34 changes: 34 additions & 0 deletions CHANGELOG.md
Original file line number Diff line number Diff line change
Expand Up @@ -6,6 +6,40 @@ The format is based on [Keep a Changelog](https://keepachangelog.com/en/1.1.0/),
and this project adheres to
[Semantic Versioning](https://semver.org/spec/v2.0.0.html).

## [1.0.2] - unreleased

### Changed

- **Device renamed from the series' colour placeholder "Rainbow" to "Chipkin
Example B-SS"** so devices from different examples in the series are
distinguishable from each other on the same BACnet network - every example
previously announced the identical Object_Name "Rainbow", which made two
examples on one subnet indistinguishable by name. Sub-object names are
unchanged. `docs/colour-table.md` (series root) updated to match.
APP_VERSION bumped 1.0.1 -> 1.0.2.

## [1.0.1] - unreleased

### Fixed

- **`Application_Software_Version` (12) and `Firmware_Revision` (44) were
hardcoded to `"1.0.0"` and never updated as the example's real version
advanced** - the same issue found and fixed in
[BACnetProfileExample-B-SCHUB-CPP](https://github.com/chipkin/BACnetProfileExample-B-SCHUB-CPP)
v1.1.13 via a real device read with CAS BACnet Explorer.
`Application_Software_Version` now returns `APP_VERSION` directly (one
source of truth, can't drift from `--version`'s own banner again).
`Firmware_Revision` is now built once at start-up, right after
`CASExampleHelper.PrintVersion()` makes the first successful native stack
call, from the CAS BACnet Stack's own
`BACnetStack_GetAPIMajorVersion()`/`GetAPIMinorVersion()`/
`GetAPIPatchVersion()`/`GetAPIBuildVersion()` (the same 4 calls
`PrintVersion()` already uses for the start-up banner) - it names the
underlying platform, not this app. Verified with a real ReadProperty
(`bacpypes3`) against the running device:
`Application_Software_Version = "1.0.1"`,
`Firmware_Revision = "6.0.21.0"`.

## [1.0.0] - unreleased

### Added
Expand Down
40 changes: 30 additions & 10 deletions Program.cs
Original file line number Diff line number Diff line change
Expand Up @@ -40,7 +40,7 @@
// object that every BACnet device must have. Each object is given a colour name
// (a convention shared across this example series):
//
// Device 389001 "Rainbow" (instance configurable with --deviceID)
// Device 389001 "Chipkin Example B-SS" (instance configurable with --deviceID)
// Analog Input 1 "Bronze" (REAL, degrees Celsius; starts at 21.5)
// Binary Input 1 "Emerald" (active / inactive)
// Multi-State Input 1 "Hot Pink" (an enumerated state, 1..3)
Expand Down Expand Up @@ -76,7 +76,7 @@ internal static unsafe class Program
// 1. Example + device configuration
// -------------------------------------------------------------------
private const string APP_NAME = "BACnet B-SS (Smart Sensor) Example - C#";
private const string APP_VERSION = "1.0.0";
private const string APP_VERSION = "1.0.2";

// The device instance. BACnet requires this to be configurable, so it
// defaults to 389001 and can be overridden on the command line with
Expand Down Expand Up @@ -105,11 +105,11 @@ internal static unsafe class Program
// the whole BACnet internetwork, and here it is a COMPILE-TIME constant.
// The device instance is runtime-configurable via --deviceID, so it is
// easy to ship two units, configure their instances correctly, and still
// have BOTH announce Object_Name "Rainbow" - a spec violation, and a hard
// have BOTH announce Object_Name "Chipkin Example B-SS" - a spec violation, and a hard
// BTL failure. In a real product Object_Name must be per-unit
// configurable too: derive it from a serial number, DIP switches, a
// config file, or add a --deviceName argument.
private const string DEVICE_NAME = "Rainbow";
private const string DEVICE_NAME = "Chipkin Example B-SS";

// The Device object's Description. Change it to what YOUR device
// actually is; this string describes this tutorial.
Expand All @@ -121,13 +121,22 @@ internal static unsafe class Program
// VENDOR_NAME - your company name; it must match VENDOR_IDENTIFIER above.
// MODEL_NAME - your model designation. This is what a building operator
// reads to identify your device in a discovery tool.
// FIRMWARE_REVISION / APPLICATION_SOFTWARE_VERSION - your real
// versions. Wire them to your build rather than
// hard-coding a number that will go stale.
// APPLICATION_SOFTWARE_VERSION - this example's own real version;
// sourced directly from APP_VERSION above, so it can't
// drift from what --version reports.
// g_firmwareRevision - the underlying CAS BACnet Stack's REAL
// version (it names the platform underneath this app,
// not the app itself). Built once at start-up, right
// after the native library is confirmed loaded - see
// Main(). Not a compile-time constant because it is
// read from the stack at runtime via the same
// BACnetStack_GetAPI*Version() calls
// CASExampleHelper.PrintVersion() uses for the
// start-up banner.
private const string VENDOR_NAME = "Chipkin Automation Systems";
private const string MODEL_NAME = "CAS BACnet Stack Example - B-SS";
private const string FIRMWARE_REVISION = "1.0.0";
private const string APPLICATION_SOFTWARE_VERSION = "1.0.0";
private const string APPLICATION_SOFTWARE_VERSION = APP_VERSION;
private static string g_firmwareRevision = "0.0.0.0";

// The sensor objects (all instance 1) and their colour names.
private const uint ANALOG_INPUT_INSTANCE = 1; // "Bronze"
Expand Down Expand Up @@ -489,7 +498,7 @@ private static bool GetPropertyCharacterString(
}
if (propertyIdentifier == CASBACnetStackAdapter.PROPERTY_IDENTIFIER_FIRMWAREREVISION)
{
return ReturnCharacterString(FIRMWARE_REVISION, value, valueElementCount, maxElementCount, encodingType);
return ReturnCharacterString(g_firmwareRevision, value, valueElementCount, maxElementCount, encodingType);
}
if (propertyIdentifier == CASBACnetStackAdapter.PROPERTY_IDENTIFIER_APPLICATIONSOFTWAREVERSION)
{
Expand Down Expand Up @@ -552,6 +561,17 @@ private static int Main(string[] args)
return 1;
}

// The native library is confirmed loaded at this point (PrintVersion()
// above made the first successful stack call). Build the Device
// object's Firmware_Revision from the stack's own real version - it
// reports the underlying CAS BACnet Stack, not this app - using the
// same 4 getter calls PrintVersion() already used for the banner.
g_firmwareRevision =
CASBACnetStackAdapter.BACnetStack_GetAPIMajorVersion() + "." +
CASBACnetStackAdapter.BACnetStack_GetAPIMinorVersion() + "." +
CASBACnetStackAdapter.BACnetStack_GetAPIPatchVersion() + "." +
CASBACnetStackAdapter.BACnetStack_GetAPIBuildVersion();

// --- Bind the BACnet/IP socket -------------------------------------
try
{
Expand Down
10 changes: 5 additions & 5 deletions README.md
Original file line number Diff line number Diff line change
Expand Up @@ -49,7 +49,7 @@ and who answers it.
## The device this example creates

```
Device 389001 "Rainbow" (Vendor 389 - Chipkin Automation Systems)
Device 389001 "Chipkin Example B-SS" (Vendor 389 - Chipkin Automation Systems)
│
├── Analog Input 1 "Bronze" Present_Value 21.5 (REAL, degrees Celsius; read-only)
├── Binary Input 1 "Emerald" Present_Value inactive (read-only)
Expand Down Expand Up @@ -82,7 +82,7 @@ which is the point of a profile example.

| Object type | Instance | Name |
|-------------|:--------:|------|
| Device | 389001 | Rainbow |
| Device | 389001 | Chipkin Example B-SS |
| Analog Input | 1 | Bronze |
| Binary Input | 1 | Emerald |
| Multi-state Input | 1 | Hot Pink |
Expand Down Expand Up @@ -223,7 +223,7 @@ Expected output:
BACnet B-SS (Smart Sensor) Example - C# v1.0.0
CAS BACnet Stack v6.0.21.0
FYI: listening on <your-ip>:47808 (broadcast <your-subnet-broadcast>)
FYI: Device 389001 ("Rainbow") ready. Vendor ID 389. Press 'h' for help.
FYI: Device 389001 ("Chipkin Example B-SS") ready. Vendor ID 389. Press 'h' for help.
```

The device listens on UDP **47808** (BACnet/IP) by default. Allow that port
Expand Down Expand Up @@ -264,10 +264,10 @@ Use a BACnet client such as the
instance **389001** (vendor **389**). It also broadcasts an I-Am at
start-up.
2. **Browse the object model** - the device shows five objects: the Device
(`Rainbow`), the three sensors, and the Network Port (`Vermilion`). Reading
(`Chipkin Example B-SS`), the three sensors, and the Network Port (`Vermilion`). Reading
the Device's `Object_List` returns all five.
3. **Read the Device** - ReadProperty `389001` -> `Object_Name` returns
`"Rainbow"`; `Protocol_Revision` returns `24`; `Description` returns the
`"Chipkin Example B-SS"`; `Protocol_Revision` returns `24`; `Description` returns the
profile description string.
4. **Read a sensor** - ReadProperty Analog Input `1` -> `Present_Value`
returns `21.5`; `Units` returns `degrees-Celsius`; `Out_Of_Service` returns
Expand Down
4 changes: 2 additions & 2 deletions docs/PICS.md
Original file line number Diff line number Diff line change
Expand Up @@ -82,7 +82,7 @@ is writable.

| Object type | Instance | Object_Name | Optional properties supported |
|---|:---:|---|---|
| Device | 389001 | Rainbow | Description |
| Device | 389001 | Chipkin Example B-SS | Description |
| Analog Input | 1 | Bronze | - |
| Binary Input | 1 | Emerald | - |
| Multi-State Input | 1 | Hot Pink | State_Text |
Expand Down Expand Up @@ -119,7 +119,7 @@ handle data in all character sets.
<!-- OBJECTS-PROPERTIES:BEGIN (generated by tools/gen-objects-properties.py from docs/objects.json - do not edit here) -->
Every object this example creates, and every REQUIRED property of each (per ANSI/ASHRAE 135-2024 clause 12 and the stack's `docs/property-profile-reference.md`), plus the optional properties the example turns on. **Served by** says who answers a ReadProperty: the **stack** generates it, or the **app** serves it from a `GetProperty*` callback in `Program.cs`. A ⚠ row is a required property the app does not serve and the stack would fill with a default - that is a defect, not a feature.

### Device 389001 "Rainbow" - the device itself; the instance is configurable with --deviceID. The stack rows are device-wide facts only the stack knows - the protocol version and revision it implements, the services and object types it was configured with, the live object list and address-binding table. The accepted rows are the stack's configured defaults for APDU limits, segmentation, system status and database revision; an application that answered them from its own constants could contradict the stack, so this example does not
### Device 389001 "Chipkin Example B-SS" - the device itself; the instance is configurable with --deviceID. The stack rows are device-wide facts only the stack knows - the protocol version and revision it implements, the services and object types it was configured with, the live object list and address-binding table. The accepted rows are the stack's configured defaults for APDU limits, segmentation, system status and database revision; an application that answered them from its own constants could contradict the stack, so this example does not

| Property | Datatype | Served by | Writable |
|---|---|---|:---:|
Expand Down
2 changes: 1 addition & 1 deletion docs/objects.json
Original file line number Diff line number Diff line change
Expand Up @@ -3,7 +3,7 @@
{
"type": "Device",
"instance": 389001,
"name": "Rainbow",
"name": "Chipkin Example B-SS",
"app": [
"Object_Name",
"Description",
Expand Down
Loading