easee_cloud: trace dynamic current around phase mode changes #225

Open

Description

@segran2

What to investigate

After a phaseMode write, Easee may reset dynamicChargerCurrent to the static maxChargerCurrent. The driver reapplies the requested limit after five seconds. Capture what Easee reports in that interval and whether measured charging current changes during an actual phase transition.

Observed on FTW Core v0.163.0-beta.1

On 2026-11-09 (CET), startup diagnostics showed phaseMode=3 and maxChargerCurrent=16 A. The driver wrote mode 3 at 03:01:32.556 and logged reapplying dynamicChargerCurrent=0 A at 03:01:37.635, 5.08 seconds later. This was a write of the existing mode at startup.

The stored samples around the write showed a dynamic limit of 0 A, measured current of about 0.007 A, and power of 0 W. The stored series had 10-second resolution, so the samples leave open whether the limit briefly reached 16 A. The cause of the earlier charging discrepancies remains unverified.

Proposed diagnostics

  • Record the phaseMode write and the delayed current-limit write with millisecond timestamps, requested values, and command results.
  • During that window, record each received SignalR observation of the dynamic limit and measured charging current with its timestamp and source. If SignalR does not provide enough observations, use bounded, targeted status reads during the transition.
  • Capture a natural phase transition during active charging. The trace should show the requested limit, Easee's reported limit, and measured charging current before the transition, during the five-second window, and after the limit is reapplied. Mark missing observations so the trace shows where the outcome is unknown.

Activity

  1. segran2 commented on Nov 12, 2026

    @segran2
    ContributorAuthor

    Follow-up from 12 November 2026, CET (UTC+1), using a local Easee driver with a startup trace. The FTW loadpoint was capped at 6 A per phase. Easee load balancing had no 6 A cap during this run. The startup phase-mode write had completed about 78 seconds before the charging order.

    Time (CET) Observation
    16:48:25.891 Easee's HTTP settings endpoint acknowledged the 6 A dynamic setting.
    16:48:25.997 Easee acknowledged the driver's automatic resume.
    16:48:26.067 Easee acknowledged Core's explicit resume. Core still had a 0 W sample.
    16:48:27.290–.291 SignalR reported 6 A and then 32 A for observation 48, both with source time 16:48:27.
    16:48:29 Easee reported a 14 A pilot and 14 A allocation on each phase.
    16:48:40 Easee measured 9.54 kW. Independent site-meter power rose at the same time.

    The trace shows 6 A writes and no 7 A boost. It establishes a real increase in charging power after the acknowledgements. It does not establish whether a resume command, a charger-side reset or another writer caused the 32 A value.

    The driver and Core account for the two resume calls. A local regression test confirms that a candidate can coalesce the immediate duplicate after a successful automatic resume and still send a later retry or a resume after a new pause. This change has not been tested on hardware. The driver writes dynamic current through the deprecated settings field; Easee documents that this endpoint only forwards changed settings. Ask Easee to identify the command or internal event that produced observation 48 at 16:48:27 CET and whether the later 6 A settings requests reached the charger.

    References

  2. segran2 commented on Nov 12, 2026

    @segran2
    ContributorAuthor

    Question sent to Easee support.

  3. segran2 commented on Nov 13, 2026

    @segran2
    ContributorAuthor

    Follow-up from 13 November 2026 (CET), using the local Easee Cloud 1.5.2 driver with startup tracing.

    • At 18:29:32, FTW requested 14 A in three-phase mode. Easee acknowledged the current setting and the resume command.
    • At 18:29:35, SignalR reported 14 A and then 32 A for observation 48 (dynamic current setting). Both updates carried the same source timestamp, 18:29:34 CET.
    • At 18:29:39, Easee reported a 6 A pilot and 6 A allocation on each phase. The first positive power sample (208 W) arrived about 6.6 seconds after the request. Measured power subsequently reached 4.17 kW.

    An earlier attempt at 18:00 showed the same brief 32 A setting report after a 15 A request. The pilot reached 6 A, while the observed power stayed at 0 W throughout the two-minute trace. The car may have been at its 80% charge limit, but the trace did not capture its SoC.

    These are charging-start traces. They do not establish what produced the 32 A setting report or what happens during a phase transition under load. The 32 A value was a reported setting, with 6 A observed on the pilot in both runs.

  4. frahlg commented on Nov 21, 2026

    @frahlg
    Member

    Thanks for the three traces. After a resume, Easee reports your limit and then 32 A for observation 48, and the pilot settles at the ordered value. They do not show what writes the 32 A. #227 sends the limit as a command, aimed at that reset. When #227 is in a build you can run, please repeat the trace on it. We also still need a trace of a natural phase change under load, with the car's SoC noted.

  5. segran2 commented on Nov 21, 2026

    @segran2
    ContributorAuthor

    Test 3 follow-up: automatic 1→3 phase transition under load (21 November 2026, CET)

    Repeated on FTW Core v0.165.1-beta.1 with the local Easee Cloud 1.5.2-derived draft carrying the command-based current reassertion from #227 and phase tracing. FTW's inferred SoC at the start was 76%.

    • With a 2.3 kW Auto request, the car was drawing 2.195 kW on one phase. Immediately before the transition, the trace showed a 10 A pilot and 10 A allocated on L3.
    • After raising the Auto request to 6.9 kW, Easee acknowledged phaseMode → 3 at 16:02:29.100. FTW's main-fuse guard temporarily set the effective order to 0 W. The driver reasserted 0 A as a command, and Easee reported 0 A pilot and 0 kW.
    • With the same Auto request still active, charging resumed once FTW allowed a positive order. At 16:03:12.057 the driver logged re-sending the 10 A limit as a command. SignalR then reported a 9 A pilot and 9 A allocated on each of L1, L2 and L3. Measured charger power subsequently reached 6.215 kW.

    This verifies that charging resumed on three phases after the automatic phase change and the temporary fuse limitation. The manual hold was released, FTW returned to its normal plan, and the test draft was reverted.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Metadata

Metadata

Assignees

No one assigned

    Labels

    No labels
    No labels

    Type

    No type

    Projects

    No projects

      Milestone

      No milestone

      Relationships

      None yet

      Development

      No branches or pull requests

      Issue actions