Easee briefly shows “Not following” between pilot confirmations during load balancing #2056
On FTW v0.165.1-beta.1 on 21 November 2026 (CET), the EV status briefly flipped from Limited by the charger’s load balancing to Not following during a steady Easee charging session.
Time (CET)
Core status
Evidence
14:14:53–14:15:23
limited / load_balancer_limit
Pilot confirmed at 8 A at 14:14:51. Measured power stayed at 5.44 kW.
14:15:23–14:15:38
not_following / power_below_target
FTW requested 13 A (8.97 kW), Easee’s dynamic limit was 13 A, and measured power stayed at 5.44 kW. The last recorded pilot was still 8 A.
From 14:15:38
limited / load_balancer_limit
The next recorded pilot confirmation, at 14:15:51, was also 8 A. Measured power remained at 5.44 kW.
The observation was during a local Easee 1.5.2-derived test draft for device-drivers#227. The supplied web client still includes the specific load-balancing message. The event history shows that the classification itself changed in Core. The trigger for the short interval remains unverified.
Expected behavior
A steady draw consistent with the previously confirmed pilot limit should avoid a transient Not following verdict when pilot confirmations are temporarily missing or delayed. If the evidence is too old to attribute the limit to Easee, show that uncertainty. Continue to report Not following for a sustained mismatch when fresh evidence supports it.
Regression case
Exercise an EV drawing about 5.44 kW against a 13 A three-phase order, with the dynamic limit at 13 A and consecutive 8 A pilot confirmations separated by a gap. Verify the displayed status during the gap and after the second confirmation.
Thanks for the clear timeline. We traced it. Core names the charger's load balancing only from the limit the driver reports. The draft driver stops reporting that limit for up to 30 s after Easee's dynamic current reading changes, so for that gap nothing explained the 5.44 kW draw, and the verdict turned to Not following at once. Your times match that gap to the second, though we have not proven the driver side on hardware.
#2062, now merged, lets a fresh pilot below the order explain a draw that matches it while the driver reports no limit. In the gap the status now reads "Limited by the charger". Only the driver can name load balancing, so Core does not claim it then. A car that takes far less than the pilot still reads Not following.
One case stays open: with no limit and a pilot older than 90 s, Core still says Not following. Showing that doubt honestly needs a driver change and new words in the clients. The fix reaches testers in the next beta.
Follow-up after #2062. I tested a local FTW v0.166.0-beta.1 build with #2062 and an additional stale-pilot fallback. When there is an accepted positive order, measured charging remains below it, the driver reports no effective limit, and the last valid pilot confirmation is older than 90 s, the local build shows “Waiting for current pilot data”.
Hardware, 21 Nov 2026 (CET). Once the fuse budget allowed the full 13 A three-phase order (8.97 kW), the charger reported a fresh 11 A pilot, no effective limit, and the car drew about 7.6 kW. FTW classified it as charger_pilot_limit (“Limited by the charger”). When the pilot rose to 13 A, measured charging rose to about 8.9 kW and the restriction cleared. The pilot was confirmed about once a minute, so the >90 s case did not occur on hardware.
Regression test and browser playback. The Core test passed, and the web client rendered the expected labels for the three simulated cases:
13 A order, no reported limit
Result
Last valid pilot older than 90 s, 5.44 kW measured
Waiting for current pilot data
Fresh 8 A pilot, 5.44 kW measured
Limited by the charger
Fresh 8 A pilot, sustained draw of about 3 kW
Not following
The stale-pilot fallback has been tested locally in Core and the web client. A naturally stale pilot with ongoing charging still needs hardware confirmation. The Easee driver's polling was unchanged for this test.
Activity
fix(ev): let a fresh pilot explain the draw while the driver withhold…
frahlg commentedon Nov 21, 2026
Thanks for the clear timeline. We traced it. Core names the charger's load balancing only from the limit the driver reports. The draft driver stops reporting that limit for up to 30 s after Easee's dynamic current reading changes, so for that gap nothing explained the 5.44 kW draw, and the verdict turned to Not following at once. Your times match that gap to the second, though we have not proven the driver side on hardware.
#2062, now merged, lets a fresh pilot below the order explain a draw that matches it while the driver reports no limit. In the gap the status now reads "Limited by the charger". Only the driver can name load balancing, so Core does not claim it then. A car that takes far less than the pilot still reads Not following.
One case stays open: with no limit and a pilot older than 90 s, Core still says Not following. Showing that doubt honestly needs a driver change and new words in the clients. The fix reaches testers in the next beta.
segran2 commentedon Nov 21, 2026
Follow-up after #2062. I tested a local FTW v0.166.0-beta.1 build with #2062 and an additional stale-pilot fallback. When there is an accepted positive order, measured charging remains below it, the driver reports no effective limit, and the last valid pilot confirmation is older than 90 s, the local build shows “Waiting for current pilot data”.
Hardware, 21 Nov 2026 (CET). Once the fuse budget allowed the full 13 A three-phase order (8.97 kW), the charger reported a fresh 11 A pilot, no effective limit, and the car drew about 7.6 kW. FTW classified it as
charger_pilot_limit(“Limited by the charger”). When the pilot rose to 13 A, measured charging rose to about 8.9 kW and the restriction cleared. The pilot was confirmed about once a minute, so the >90 s case did not occur on hardware.Regression test and browser playback. The Core test passed, and the web client rendered the expected labels for the three simulated cases:
The stale-pilot fallback has been tested locally in Core and the web client. A naturally stale pilot with ongoing charging still needs hardware confirmation. The Easee driver's polling was unchanged for this test.